DN-6619:A2. 4/13/2012 — Page 1 of 4 411 Series Slave Digital Alarm Communicator Transmitters Miscellaneous DN-6619:A2. K-95 General The 411 Series DACTs are compact, multifaceted, slave Digi- tal Alarm Communicator Transmitters designed for a variety of fire, security, and non-fire applications. The series features the 411 and 411UD, which provide three and four monitoring channels (inputs) respectively. These slave DACTs are a solu- tion for applications that require an existing (or new) fire alarm control panel (FACP) to transmit system status to an off-site monitoring facility for Central or Remote Station compliance. Due to extremely flexible programming options, the 411 Series slave DACTs are also ideal for monitoring non-fire and security control panels.

With fifteen selectable transmission formats (including ADEMCO Contact ID) compatibility with virtually all Digital Alarm Communicator Receivers (DACR) is ensured. Programming can be accomplished on-site with a hand-held programmer (PRO-411), or remotely (411UD only) using the PK-411UD programming utility. This Windows®-based remote upload/download software package permits system interroga- tion and revision from a remote site. Features.

Notifier sfp 10ud installation manual

Three (411) or four (411UD) monitoring channels (inputs). Inputs may be individually programmed to monitor the host control panel for: – Fire Alarm. – Fire Trouble. – Fire Supervisory.

Fire

Notifier 1024 Datasheet

– Process Monitoring. – AC Power Loss. – Security Alarm. – Other (Fire and Non-Fire Events). Fully supervised trigger inputs require a contact closure for activation. 12- or 24-VDC operation, jumper-selectable.

Industry-first, UL recognized, “dialer-runaway” prevention feature. Dual-line, rotary or touch-tone-dial DACT interfaces to pub- lic switched telephone network (leased phone lines are not required). Includes 15 reporting formats, including the popular ADEMCO Contact ID format. Capable of transmitting the following DACT information, in addition to vital system status of the host control panel: – DACT troubles. – Telephone line 1 and 2 voltage fault.

– Primary or Secondary Central Station communication fault. – System off-normal. 7th and 8th grade academy.

Sfp 1024 User Manual

Notifier sfp 2404 manual

– 24-hour normal test. – 24-hour abnormal test. Long-distance Carrier Access Code (CAC) compliant, accepting up to 20-digit Central Station telephone numbers. Fully programmable transmittal codes for fire, security, pro- cess monitoring, and others. Field-programmable with PRO-411 hand-held programmer.

Programmable from remote site with optional PK-411UD programming software (model 411UD only). View 411 Series status offsite in real time, with optional PK- 411UD programming software, without ever compromising monitoring protection at the protected premises (model 411UD only). Programming sequence based on NOTIFIER’s popular SFP-1024 Control/Communicators. Integral piezo sounder (both models) with local silence switch (model 411UD only).

One Form-C relay, fully programmable (model 411UD only). Complies with NFPA 72 (Central Station and Remote Sta- tion DACT only - not polarity reversal Fire Alarm Systems). Surface Mount Technology (SMT). Extremely compact enclosure, measuring only 6.75' (17.145 cm) W x 4.40' (11.176 cm) H x 1.05' (2.667 cm) D. Shares identical footprint with 911 Series for replacement purposes. Host Panel Compatibility Host panels must include AC Fail Delay option to meet NFPA Central Station Requirements.

Panels with this feature include RP-1001, RP-1002, RP-2001, RP-2002, System 500, System 5000, AFP-200, AFP-300, AFP-400, NFS-320, NFS-640, NFS2-640, AFP1010, AM2020, NFS-3030, and NFS2-3030. Housing The 411 Series DACTs are fully enclosed in a compact hous- ing measuring only 6.75' (17.145 cm) W x 4.40' (11.176 cm) H x 1.05' (2.667 cm) D. The housing enclosure consists of an aluminum backbox painted red with a matching cover secured by two captive screws. The overlay includes large areas to independently mark programming options for the three or four channels (inputs), relay, and also includes printed terminal and diagnostic LED designations. The overall compact size of the enclosure permits mounting of these DACTs in virtually any control panel’s enclosure, or alternately, adjacent to the host control panel. Phone Line Connections Two modular phone connections on the 411 Series are acces- sible with the cover in place and provide connections for two 6619p h1.J P G.